Log Book for March 22, 2008
Engineering Report
Elisha Sanders Reporting
Generator/Electricity:
Wendy
Hobbs Meter: 3813.5 hrs [ +21.8 hrs since yesterday ]
Voltage: 117 VAC
[*] Frequency: 56 Hz
Oil Level: 7/8
Oil Pressure: 30 PSI
[*] Water Drained: no
Notes/Comments: The generator was accidentally left on the "prime/run" setting (feeding from main tank). Thirty minutes after it started we noticed that the batteries were no longer charging and that the voltage coming off of the generator was fluctuating between 80-120V. Once the generator was switched over to the Aux tank the voltage was constant around 120V.
Xantrex Inverter/Dynasty Batteries:
Time Voltage (Temp Comp) Load Temp Generator Running? 1306 26.6V 7.6A 9C yes 1535 26.6V 9.5A 11C yes 1655 26.7V 16.8A 11C yes 2015 26.8V 6.6A 12C yes
Notes/Comments: The high load at 1655 was due to running the water heater.
Fuel Status (as of 17:51):
Diesel:
Approximate Reading: 1/2
Propane Tank:
Approximate Reading: 56% (560 gallons = 2119.8 L)
Gasoline:
Quantity Remaining: 37 gallons = 140.1 L [ no change since yesterday ]
Oil:
[*] GenSet Quantity: 15 quarts [ no change since yesterday ]
ATV Quantity: 8 quarts [ no change since yesterday ]
[*] V'ger Quantity: 0 quarts [ no change since yesterday ]
Water Status:
Outside Potable Water Tank Level: 310 gallons = 1173.5 L
Trailer Potable Water Tank Level: 24 inches from the base
[**] Potable Water Meter Reading: 27472.9 gallons = 103995.9 L [ +100.9 gallons since yesterday ]
Out to Toilet Meter Reading: 8359.2 gallons = 31642.9 L [ +7.9 gallons since yesterday ]
In to GreenHab Meter Reading: 7829 gallons = 29635.9 L [ no change since yesterday ]
Dishwasher Runs: 0
GreenHab:
Crops Watered: no
Crop Condition: Seems healthy.
Observatory:
[**] Voltage (STV on): NO VALUE SUPPLIED
Transportation:
Kawasaki ATVs
ATV 1 Used: no Oil Checked: no Tire Status: ok
ATV 2 Used: no Oil Checked: no Tire Status: ok
ATV 3 Used: no Oil Checked: no Tire Status: ok
Mars Surface Suits: Suits used: 4,5,3,S-1 PLSS used 1,4,5,3 Helmets used 1,2,3,5
GreenHab: inside time temp hum 1522 82F 14% 1806 63F 16%
outside time temp hum 1522 62.6F 11% 1806 54.7F 10%
We have a working grey water trickle system in the GreenHab!! Thanks to Dan we found a brand new identical pump sitting in the upstairs loft. We replaced the broken left pump in the GreenHab, keeping the inlet filter (after a thourough cleaning). We replaced the screen filter on the end of the inlet tube as well to insure that it will not burn out this pump in the same way. Switching it on we got great flow and opening the valve we started flow to AT1 (which in turn trickled down to AT2, AT3, and filled an almost empty AT4). As a result we have depleted most of the grey water stores under the hab. Consequently I have mandated showers for all of the crew (we are all happy).
Also it seems that the bubbler that goes into AT2 and AT3 was not working although it was receiving power. We switched the tubes to another bubbler that was also hanging from the rafters which worked very well.
Observatory: Dan sending info about rope.
|
|
|